Safety Switch STPA...
Inspection and service
WARNING
Danger of severe injuries due to the loss of the
safety function.
If damage or wear is found, the complete switch
f
and actuator assembly must be replaced. Re-
placement of individual parts or assemblies is
not permitted.
Check the device for proper function at regular
f
intervals and after every fault. For informa-
tion about possible time intervals, refer to
EN ISO 14119:2013, section 8.2.
Inspection of the following is necessary to ensure
trouble-free long-term operation:
Correct switching function
f
Secure mounting of all components
f
Damage, heavy contamination, dirt and wear
f
Sealing of cable entry
f
Loose cable connections or plug connectors.
f
Info: The year of manufacture can be seen in the
bottom right corner of the type label.
Exclusion of liability and warranty
In case of failure to comply with the conditions for
correct use stated above, or if the safety regula-
tions are not followed, or if any servicing is not
performed as required, liability will be excluded and
the warranty void.
Notes about
The following information applies to devices
with cable entry:
For use and application as per the requirements
of
a copper wire for the temperature range
60/75 °C must be used.
The following information applies to devices
with plug connector:
This device is intended to be used and applied with
a Class 2 power source in accordance with UL1310.
Connecting cables for safety switches installed at
the place of use must be separated from all moving
and permanently installed cables and un-insulated
active elements of other parts of the system that
operate at a voltage of over 150 V. A constant
clearance of 50.8 mm must be maintained. This
does not apply if the moving cables are equipped
with suitable insulation materials that possess an
identical or higher dielectric strength compared to
the other relevant parts of the system.
Declaration of conformity
The product complies with the requirements accord-
ing to Machinery Directive 2006/42/EC.
The EU declaration of conformity can be found at
www.euchner.com. Enter the order number of your
device in the search box. The document is available
under Downloads.
Service
If servicing is required, please contact:
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
70771 Leinfelden-Echterdingen
Germany
Service telephone:
+49 711 7597-500
E-mail:
support@euchner.de
Internet:
www.euchner.com
Technical data
Parameter
Value
Housing material
Reinforced thermoplastic
Degree of protection acc. to
EN IEC 60529
Cable entry
IP67
Plug connector SR11
IP65
Mechanical life
1 x 10
operating cycles
6
Ambient temperature
-20 ... +55 °C
Degree of contamina-
tion (external, acc. to
3 (industrial)
EN IEC 60947-1)
Installation position
Any
Approach speed, max.
20 m/min
Extraction force (not locked)
30 N
Retention force
20 N
Actuating force, max.
35 N
Actuation frequency
1,200/h
Switching principle
Slow-action switching contact
Contact material
Silver alloy, gold flashed
Connection
STP...M
Cable entry M20 x 1.5
STP...SR11
Plug connector SR11, 11-pin+PE
(PE not connected)
Conductor cross-section
0.34 ... 1.5 mm²
(flexible/rigid)
Operating voltage for optional
L024 24 V
LED indicator
Rated insulation voltage
STP...M
U
= 250 V
i
STP...SR11, STP... with
escape release
U
= 50 V
i
Rated impulse withstand voltage
STP...M
U
= 2.5 kV
imp
STP...SR11
U
= 1.5 kV
imp
Conditional short-circuit
100 A
current
Switching voltage, min., at
12 V
10 mA
Utilization category acc. to EN IEC 60947-5-1
STP...
AC-15 4 A 230 V /
DC-13 4 A 24 V
STP...SR11, STP... with
AC-15 4 A 50 V /
escape release
DC-13 4 A 24 V
Switching current, min., at
1 mA
24 V
Short circuit protection
(control circuit fuse) acc. to
4 A gG
EN IEC 60269-1
Convent. thermal current I
4 A
th
Solenoid operating voltage/solenoid power consumption
STP...024
AC/DC 24 V (+10%/-15%) 8 W
STP...110
AC
110 V (+10%/-15%) 10 W
Duty cycle
100%
Locking force
F
max
ACTUATOR-S-G..., HINGED
ACTUATOR-S-...
2,500 N
ACTUATOR S-WQ-...
2,000 N
ACTUATOR S-W-...
1,500 N
ACTUATOR-S-WT-...,
ACTUATOR-S-WQT-...
1,000 N
Characteristics acc. to EN ISO 13849-1
Monitoring of guard locking and the guard position
B
5 x 10
10D
6
at DC-13 100 mA / 24 V
8
F
Zh
2,000 N
1,500 N
1,100 N
700 N