The AutoPing feature allows the AR to automatically detect failed equipment and perform a timed
reboot or other power control function (like turning on an indicator or siren). First specify one or two IP
addresses to be periodically pinged. When the AR no longer receives a response from these addresses, the
programmed power control function is actuated. AND or OR logic can be applied to the two addresses, so
that both (AND) or either (OR) must fail in order to trigger the selected action.
Examples:
Server monitor: AR is installed with the device it
monitors and automatically reboots if there is no
response. Ideal for Kiosks and Servers.
Service monitor: AR is installed with the device to be
rebooted, but pings a remote host to test the
communication channel. Ideal for DSL/Cable Modem
verification.
AR monitors a network device, and powers up an alarm
or redundant system when there is no response. Ideal for
Hot Standby Servers, Environmental Control, Alert for
any network failure.
IP Address 1 and 2: Enter the IP
address(es) of the device(s) to be pinged.
Frequency 1 and 2:
999 seconds).
Fail Count 1 and 2: Enter the number of times the ping must consecutively fail
(1-999) before the selected action is triggered.
Mode: Select the logic to be used (AND, OR, or Single). With AND logic, both AutoPings must
exceed their fail count to trigger the action. With OR logic, the action will be triggered if either
AutoPing exceeds its fail count. With Single, only AutoPing 1 is used.