Action: Select the action to be triggered.
None
Power On – Latch
Power On – Follow
Power Off – Latch
Power Off – Follow
Power Cycle
Power Cycle - Once
Restart: This setting delays the restart of the AutoPing tests after the Action is completed. This
setting allows time for the boot sequence of the failed device to complete.
© AMETEK Electronic Systems Protection, Inc. | Soporte técnico: 800-645-9721 | surgex.com
SA-82-AR
AutoPing not used
Upon triggering, AR will power on and remain so until
changed via web, telnet, or DxP.
Upon triggering, AR will power on. When the ping
response returns, AR will power off.
Upon triggering, AR will power off and remain so until
changed via web, telnet, or DxP.
Upon triggering, AR will power off. When the ping
response returns, AR will power on.
Upon triggering, AR will cycle the power. AR will then
wait for (Ping Frequency x Fail Count) seconds; if the response does
not return, the power will be cycled again. This will repeatedly
continue until the ping response returns or AutoPing is turned off.
Ensure that the AutoPing frequency is longer than the time
required to reboot the device.
Upon triggering, AR will cycle power one time. It will not cycle again
automatically until the ping response returns and is lost again.