Setting automatic closing time
The timer starts from the gate open state and continues for the set time. Once the set time is reached, the gate closes
automatically. The timer count restarts if a photocell is triggered.
Pause time settable from 00 to 90 s.
Pause time settable from 2 to 9 min.
Enabling of management for opening with automatic re-closure exclusion
If enabled, the exclusion of automatic re-closure only applies for the command selected via the parameter. For example:
if you set
, automatic re-closure is excluded following an AP command, but it is activated following a PP or PED
command.
NOTE: The command has open-stop-close or close-stop-open sequence activation function.
Disabled.
An AP (opening) command activates the opening manoeuvre. When the gate is fully open, automatic reclosure is exclu-
ded. A subsequent AP (open) command activates the closing operation.
A PP (step-by-step) command activates the opening manoeuvre. When the gate is fully open, automatic reclosure is
excluded. A subsequent PP (step-by-step) command activates the closing operation.
A PED (partial opening) command activates the partial opening operation. Automatic reclosure is excluded. A subse-
quent PED (partial opening) command activates the closing operation.
Setting reverse time after activation of sensing edge or obstacle detection (crush
prevention)
This sets the reverse manoeuvre time after activation of the sensing edge or the obstacle detection system. The gate co-
mes to a stop after reversal dues to activation of the sensing edge or obstacle detection system at the end of manoeuvre
deceleration speed. As a result, the effective reversal manoeuvre time is slightly longer than the set time.
From 0 to 60 s.
Setting motor torque
Increasing or decreasing the value of the parameter increases or decreases motor torque and, as a result, adjusts
obstacle detection sensitivity.
Use values below
ONLY for particularly lightweight installations not exposed to severe weather conditions (strong
winds or very cold temperatures).
= -35%;
= -25%; 03= -16%;
= default motor torque setting.
= +8%;
= +16%;
= +25%;
Setting obstacle impact force sensitivity
If the reaction time to obstacle impact force is too long, reduce the value of the parameter. If the impact force exerted
on obstacles is too high, reduce the value of parameter
Low motor torque:
= minimum obstacle impact force ...
N.B.: only use these settings if the medium motor torque values are not suitable for the installation.
Medium motor torque. Recommended setting for adjusting force settings correctly.
= minimum obstacle impact force ...
70% of maximum motor torque, 1 s of reaction time. Sensing edge is compulsory.
80% of maximum motor torque, 2 s of reaction time. Sensing edge is compulsory.
Maximum motor torque, 3 s of reaction time. Sensing edge is compulsory.
Maximum motor torque, 5 s of reaction time. Sensing edge is compulsory.
Setting start acceleration during opening and closing
See chapters 14 and 15
= the gate accelerates rapidly at start of manoeuvre ...
manoeuvre.
Enabling maximum torque boost at start of manoeuvre
If this parameter is enabled, each time the motor starts a manoeuvre, maximum torque is produced for a maximum of
5 seconds, or for the time necessary for the gate to open by approximately 65 cm.
N.B: in the case of High Speed and Reversible motors, a motor boost mode is implemented for 2 seconds after each
gate start, regardless of the setting of parameter
Disabled.
Enabled at start of opening manoeuvre only (including position recovery). The motor starting current function is only
enabled for closing manoeuvres if the gate position is known and the gate is over to 2 metres from the completely
closed position.
Enabled for all starts (including position recovery).
= -8% (reduced motor torque = increased sensitivity).
= +35% (increased motor torque = reduced sensitivity).
.
= maximum obstacle impact force
= maximum obstacle impact force.
= the gate accelerates slowly and progressively at start of
.
67