M9316-xxx-xZ / M9320-xxx-x / M9335-xxx-x
Technical Specifications
Product Code
• Code produit • Produktcode
• Codice prodotto • Código de producto
• Productcode • Produktkod • Kód výrobku
• Kod produktu • Код продукта
• Código de produto • 产品代码 • 製品コード
Control Type
• Type de commande • Steuerungsart
• Tipo di comando • Tipo de control
• Besturingstype • Kontrolltyp • Typ řízení
• Typ sterowania • Тип управления
• Tipo de controlo • 控制类型 • 制御タイプ
Power
Transformer
Input
• Entrée • Eingang • Ingresso • Entrada • Ingang • Ingång
• Vstup • Wejście • Вход • Entrada
• 输入 • 入力
Impedance
• Impédance • Impedanz • Impedenza
• Impedancia • Impedantie • Impedans
• Impedance • Impedancja
• Импеданс • Impedância • 阻抗 • インピーダンス
Feedback
• Rétroaction • Rückmeldung • Ritorno
• Realimentación • Feedback • Feedback
• Zpětná vazba • Sprzężenie zwrotne
• Обратная связь • Feedback • 反馈 • フィードバック
Torque
M
Rotation Range
Rotation Time
Compliance
M9320-AUA-1
M9320-AUA-2
M9320-AUA-3
On/Off, Floating
Nominal 230 VAC
Nominal 120 VAC
50/60 Hz: 0.04 A
60 Hz: 0.05 A Running
Running
AC 100...240 V (AC 85...240 V), 50/60 Hz
20 Nm (180 lb. in)
Mechanically Limited to 35...95° ±3° in 5° increments
90 s
United States: UL Listed, CCN XAPX, File E27734; to UL 60730-1: Automatic Electrical
Controls for Household and Similar Use, Part 1; and UL 60730-2-14: Part 2, Particular
Requirements for Electric Actuators. Plenum Rated (UL 2043). Suitable for use in Other
Environmental Air Space (Plenum) in accordance with section 300.22 (c) of the National
Electrical Code.
Canada: UL Listed, CCN XAPX7, File E27734; to CAN/CSA E60730-1:02: Automatic
Electrical Controls for Household and Similar Use, Part 1; and CAN/CSA-E60730-2-14,
Particular Requirements for Electric Actuators.
Europe: CE Mark
Johnson Controls declares that these products are in compliance with the essential
requirements and other relevant provisions of the EMC Directive and Low Voltage Directive.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
14
M9335-AUA-1
M9335-AUA-2
M9335-AUA-3
On/Off, Floating
Nominal 230 VAC
Nominal 120 VAC
50/60 Hz: 0.04 A
60 Hz: 0.05 A Running
Running
100k ohm
35 Nm (310 lb. in)
150 s
34-636-2502 Rev. A