Descargar Imprimir esta página

baltur TBL 45 LX Manual De Instrucciones De Uso página 11

Quemadores de gasoleo

Publicidad

Idiomas disponibles

Idiomas disponibles

PIPES FOR LIGHT OIL BURNERS MODEL TBL 45LX - 75LX
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
10 Bottom valve
GRAVITY SUPPLY SYSTEM
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
PUMP AXIS
DROP-TYPE SYSTEM WITH SUPPLY FROM THE TANK TOP
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
PUMP AXIS
SUCTION - TYPE FEEDING SYSTEM
PUMP AXIS
H = Difference in level between level in the tank and the pump axis.
L = Maximum length of suction pipe including the vertical lift.
0006081324_201612
6 Suction pipe
7 Return pipe
8 Automatic fuel interception
device at burner shut off
9 Non-return valve
H
meters
1
1,5
2
2,5
3
8 Automatic fuel interception
device at burner shut off
9 One-way valve
10 Bottom valve
H
meters
1
1,5
2
2,5
3
meters
0,5
1
1,5
2
2,5
N.B. For any missing devices in the piping,
follow existing regulations.
For each bend or valve deduct 0,25 m.
11 / 82
Total meters
meters
Ø i. 14 mm.
30
35
35
40
40
Total meters
meters
Ø i. 14 mm.
30
35
35
40
40
P = 3,5 m. (max.)
Total meters
H
meters
Ø i. 14
Ø i. 16
mm.
mm.
26
45
22
38
19
31
14
25
11
19
E
N
G
L
I
S
H

Publicidad

loading

Este manual también es adecuado para:

Tbl 75 lx35730010