Wall mounting:
The supply line must be positioned using the
drilling template provided or the figure "Drilling di-
mensions [mm]".
1 "5.5 Installing the product on the wall" [} 14]
Pedestal mounting:
This is available from MENNEKES as an accessory.
1 See installation manual for the pedestal
5.2.2 Protective devices
The tasks described in this section may only
be carried out by a qualified electrician.
The following conditions must be met when in-
stalling the protective devices in the upstream elec-
trical installation:
Residual current device
n National regulations must be observed
(e.g. IEC 60364‑7‑722 (in Germany DIN
VDE 0100‑722)).
n A differential current sensor for DC resid-
ual current monitoring > 6 mA in accord-
ance with IEC 62752 is integrated in the
product.
n The product must be protected by a re-
sidual current device. As a minimum, a
type A residual current device must be
used.
n No other circuits may be connected to
the residual current device.
Supply line fuse (e.g. miniature circuit breaker,
NH fuse)
n National regulations must be observed
(e.g. IEC 60364‑7‑722 (in Germany DIN
VDE 0100‑722)).
n The fuse for the supply line must be de-
signed for the product, taking account,
among other considerations, of the rating
plate, the required charging power and
the supply line (line length, cable cross-
section, number of outer conductors, se-
lectivity).
n The following applies for AMTRON®
4You 100 11: The rated current of the fuse
for the supply line must not exceed 20 A
(with C characteristics).
n The following applies for AMTRON®
4You 100 22: The rated current of the
fuse for the supply line must not exceed
40 A (with C characteristics).
Shunt release
u Check whether a shunt release is legally pre-
scribed in the country of use.
1 "2.2 Intended use" [} 3]
n The shunt release must be positioned
next to the line circuit breaker.
n The shunt release and the line circuit
breaker must be compatible with each
other.
5.3
Transporting the product
ATTENTION
Material damage due to improper transportation
Collisions and impacts may damage the product.
u Avoid collisions and impacts.
u Transport the product to the place of installa-
tion in the packed condition.
u Set the product down on a soft base.