Operating Conditions - Aros APPENDIX 1500 Manual De Instrucciones

Inversor fotovoltaico para conexión en red
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Operating
conditions
Isolation failure
GFCI active
Grid failure
Abnormal Grid
Impedance
No utility
Input voltage too high
Consistent failure
Temperature too high
Output relay failure
Output DC injection
too high
EEPROM problem
Communication
between
microprocessors
DC bus voltage is too
high
DC bus voltage is too
low
2.5V reference
voltage inside
problem
- ENGLISH -
Message in
English
Isolation fault
Ground I fault
Grid fault
Impedance fault
No Utility
PV over voltage
Inverter fault
Consistent fault
Over temperature
Relay Failure
DC INJ High
EEPROM Failure
SCI Failure
High DC Bus
Low DC Bus
Ref 2.5V Fault
Description
PV generator leakage to ground or input
surge voltage protections have activated
The
leakage
current
conductor is too high
The measured grid data is outside of the
required specification (voltage & frequency)
Table 3
(See "
" in appendix)
1. The grid impedance is higher than the
permissible value
2. The grid impedance change (ΔZ) is
higher than the maximum limit
The utility is not available
The input voltage is higher than "Max open
DCV"
The readings of output AC voltage,
frequency, leakage, DC current injection are
not
consistent
microprocessors.
The internal temperature is higher than the
recommended value
The relay between the inverter and the grid
is faulty
The output DC current injection is too high
The internal EEPROM has a data access
error
The communication between the internal
MCU is abnormal
The internal DC BUS voltage is higher than
expected
The internal DC BUS voltage is lower than
expected
The internal 2.5V reference voltage is
abnormal
on
the
ground
between
the
Page 31
two

Publicidad

Tabla de contenido
loading

Tabla de contenido