A) Before commencing any installation work, check that the proposed installation will comply with Building Code
requirements and Local Consent Authority rules that may apply to vented heaters in your area. (Check your
Local Authority website, or consult your Installer / Supplier.)
B) The Flue Pipe is designed to be installed through the wall of any conventional building cladding, including
Brick, Hebel, Linear, Gibraltar and Plaster Board, Tiles, Weatherboard, Plastered Polystyrene, and metal
profiles etc.
C) The FF-95 heater is designed to be operated at altitudes up to 1,000 m, above sea level. For installation at
altitudes between 1,000 m and 1,500 m, adjustments by authorized serviceperson is necessary. Consult your
supplier for advice.
1. Select heater location. Ensure minimum clearances as indicated
below between heater and nearest combustible materials. Provide
service access to clean the rear circulation air filter, fuel strainer and
red float release button.
2. Ensure the outdoor flue discharge area is clear of anything that
might be affected by the hot flue exhaust gas.
(See Fig. 2 and 3.)
The Flue Pipe (as in Fig. 2), is for wall thickness from 130 mm to 320
mm.
3. Ensure the heater is level by using the "plumb bob" located at
the right side of the heater.
When viewed from above, the plumb bob "weight" should be
within the circle. If not, adjust the heater "feet" untril the plumb
bob weight is within the circle.
4. A room temperature sensor is provided with approx. 2.5 m long extension wire.
It is located on the rear of the cabinet. Make sure that the extension wire is not
touching the exhaust pipe. The room temperature sensor can be installed with a
wood screw. Screw down the wood screw provided with the heater into the desired
location on the wall. Hook the back of the room temperature sensor.
NOTE: Choose a location for the sensor that is not in the path of direct sunlight,
drafts or the flow of warm air from the heater.
Read installation manual before installing heater.
GB
19
INSTALLATION OF HEATER AND FLUE PIPE
Combustible object
Combustible object
More than 60 cm
Noncombustible object
45˚
More than 30 cm
Flue Pipe
More than 20 cm
Fig. 2
More than 60 cm
* Be sure this
clearance will
be maintained
after snow-
falls, etc.
Flue Pipe Installation
Plumb bob as viewed from above
More than
60 cm
More than
30 cm
More than
150 cm
Fig. 1
More than 45 cm
More than
45 cm
Fig. 3
Good
Weight
Circle
Bad
ENGLISH
More than
10 cm
More than
30 cm