TABLE OF PIPELINE FOR BT 40 - 55 - 75 - 100 DSN - 4T
WITH FUEL AT 5° AT 50° C (40° AT THE 5° C PUMPING TEMPERATURE)
Pump axis
SIPHON FEED SYSTEM WITH FEED FROM THE TOP OF THE TANK
Pump axis
GRAVITY FEED SYSTEM
Pump axis
SUCTION FEED SYSTEM
N.B. Comply with existing regulations regarding apparatus required in
the pipeline system
H - Height difference between minimum fuel tank level and pump axis.
L - Total length of pipeline, including vertical lenght. Subtract 0,25 mt.
for every elbow or gate valve.
0006080547_201610
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
6 Suction pipe
7 Return pipe
8 Automatic fuel interception
device at burner shut off
9 Non-return valve
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
8 Automatic fuel interception
device at burner shut off
9 One-way valve
10 Bottom valve
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
10 Bottom valve
12 / 38
H
Total length
meters
meters
Ø = 1"
1
31
2
35
2,5
35
3
35
Maximum intake and return
pressure = 1 bar
H
Total length
meters
meters
Ø = 1"
1
31
2
35
2,5
35
3
35
Maximum intake and return
pressure = 1 bar
Dimension P = 3,5 m. (max.)
H
Total length meters
meters
Ø = 1"
Ø 1" 1/4
0,5
22
35
1
17
35
1,5
12
35
2
7
21
2,5
3
8
3
-
-
3,5
-
-