26 EN – R1...R4 Quick installation guide
Select the power cables
Size the power cables according to local regulations to carry the nominal current
given on the type designation label of your drive.
Ensure the cooling
R1-
R4
See table
I IEC, UN = 400 V
R5
page 21) for the heat dissipation. The allowed operating temperature range of the
drive is -15 to +50 °C (+5 to +122 °F). No condensation or frost is allowed. For more
R6-
information on the ambient temperature and derating, see chapter Technical data in
R9
ACH580-01 (0.75 to 250 kW) hardware manual (3AXD50000044839 [English]).
Protect the drive and input power cable
EN
See tables
III gC
23) for the fuses.
DA
If you use gG fuses, make sure that the operating time of the fuse is below
0.5 seconds. Follow the local regulations.
DE
Install the drive on the wall
ES
See figure
R1...R4 Figures A
FI
Check the insulation of the power cables and the motor
FR
Check the insulation of the input cable according to local regulations before
IT
connecting it to the drive.
See figure
B1
on page 403.
NL
1. Check the insulation of the motor cable and motor when the cable is disconnected
PL
from the drive. Measure the insulation resistance between each phase conductor
and then between each phase conductor and the Protective Earth conductor
PT
using a measuring voltage of 1000 V DC. The insulation resistance of a typical
motor must exceed 100 Mohm (reference value at 25 °C or 77 °F). For the
RU
insulation resistance of motors, see the manufacturer's instructions.
Note: Moisture inside the motor casing will reduce the insulation resistance. If
SV
moisture is suspected, dry the motor and repeat the measurement.
TR
ZH
on page
(on page 22) and
IV uR or aR
on page 403.