Connect The Control Cables - ABB ACH580-01 Guía Rápida De Instalación Y Puesta En Marcha

Ocultar thumbs Ver también para ACH580-01:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 203

Connect the control cables

See figure
G
on page 409. It shows an example with one analog signal cable and one
digital signal cable. Make the connections according to the default configuration in
use. The default connections of the HVAC default configuration are shown in section
Default I/O connections
1. Remove the front cover, if not already removed. See section
and open the cover
Example of connecting an analog signal cable:
2. Cut an adequate hole into the rubber grommet and slide the grommet onto the
cable. Slide the cable through a hole in the cable entry and attach the grommet to
the hole.
3. Ground the outer shield of the cable 360 degrees under the grounding clamp.
Keep the cable unstripped as close to the terminals of the control board as
possible. Ground also the pair-cable shields and grounding wire at the SCR1
terminal.
4. Route the cable as shown in the figure.
5. Connect the conductors to the appropriate terminals of the control board and
tighten to 0.5...0.6 N·m (0.4 lbf·ft).
6. Tie all control cables to the provided cable tie mounts.
on page 180.
on page 175.
EN – R5 Quick installation guide 179
Switch off the power
R0-
R4
R5
R6-
R9
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH
ZH

Publicidad

Tabla de contenido
loading

Tabla de contenido