baltur COMIST 180 Manual De Instrucciones página 60

Quemadores mixtos gas
Ocultar thumbs Ver también para COMIST 180:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

INSTRUCTIONS FOR HONEYWELL GAS VALVES
UNIVERSAL GAS VALVES TYPE: VE 4000A1
(....A .... = OPENING - CLOSURE, RAPID)
The VE 4000A1 valves are Class A solenoid valves, normally clo-
sed. They may be used as ON/OFF valves in the supply trains with
Natural Gas, Manufactured Gas or GPL, on burners or combustion
installations.
They are provided with M.I. and CE Approval for EN161.
FEATURES
- Valves normally closed
- Without flow regulator
- Rapid opening and closing
INSTRUCTIONS FOR HONEYWELL GAS VALVES
UNIVERSAL GAS VALVES TYPE: VE 4000B1 (..B.. =
OPENING - CLOSURE, RAPID. FLOW REGULATOR)
FEATURES
Valve normally closed
With flow regulator
Rapid opening and closing
The VE4000B1 valves are Class A solenoid valves, normally closed.
They may be used as ON/OFF valves in the supply trains with Natural
Gas, Manufactured Gas or GPL, on burners or combustion plants.
They are provided with M.I. and CE Approval for EN 161.
ADJUSTMENT
For models VE 4000B1 (see fig. 1)
Adjustment to the flow
- Remove the cover from the upper section of the coil.
- Insert a hexagonal Allen key into the central section at the top.
- Turn clockwise to decrease the flow or anti-clockwise to increase it.
- Replace the cover and tighten it.
ATTENTION
The adjustment must only be carried out by qualified personnel.
To close valve it's necessary that the coil's voltage at its leads
is 0 volt.
The flow regulator of the VE 4100 valve series is situated in
the lower section.
fig.1
22 / 36
0006080095_201207