SQN 30.111 A3500

Motor-cam shaft coupling cutting out pin.
The switching-off of the motor and shaft
connection can be obtained by pushing.
PREVENTILATION WITH AIR OPEN (2
CLOSED WITH BURNER IN STOP POSITION
1
2nd Flame valve connection cam (must be adjusted in a
position between the 1st flame and the 2nd flame cam)
2
Air regulation cam 1° flame
3
Close air shutter cam with burner in stop position
4
Air regulation cam 2nd flame
FLAME POSITION) AIR
nd
In order to modify the cams regulation it's necessary to intervene
on the relative red rings. Pushing by sufficient strength,in the sens
one desires, each red ring can turn in respect to the reffering scale.
The pointer of the red ring indicates on the respective reffering
scale the rotation angle set for each cam.
31 / 36
0006080095_201207
4
3
2
1