RFL Electronics RFL 9300 Manual De Instruccion página 147

Sistema de comparación de carga
Tabla de contenido

Publicidad

Tabla6-6. Read mode, parámetros del sistema de comparación de carga RFL 9300 para tres terminales
No.
Display
Definition
...
Moving dots
RFL 9300 is in STANDBY mode. Display controller parameter; not user-selectable.
0
EXIT
Exit to STANDBY mode. Display function; can be set to either ENABLE or DISABLE. (1)
1
PngPng 1
Value of ping-pong (round-trip delay) for remote 1.
2
PngPng 2
Value of ping-pong (round-trip delay) for remote 2.
5
LOC IA
Local Phase A current.
6
LOC IB
Local Phase B current.
7
LOC IC
Local Phase C current.
8
LOC 3I0
Local 3I0 current.
9
REM1 IA
Remote 1 Phase A current.
10
REM1 IB
Remote 1 Phase B current.
11
REM1 IC
Remote 1 Phase C current.
12
REM1 3I0
Remote 1 3I0 current.
13
REM2 IA
Remote 2 Phase A current.
14
REM2 IB
Remote 2 Phase B current.
15
REM2 IC
Remote 2 Phase C current.
16
REM2 3I0
Remote 2 3I0 current.
17
RCV ADD1
Remote 1 Rx address. (2)
18
RCV ADD2
Remote 2 Rx address. (3)
19
ALARMS
Present alarm status (four alarms).
20
PH BIAS
Phase bias. Programmable; see table 6-10 for more information.
21
GND BIAS
Ground bias. Programmable; see table 6-10 for more information.
22
BIAS CTL
Bias control. Programmable; see table 6-10 for more information.
23
GND DLY
Enable/disable ground delay. Programmable; see table 6-10 for more information.
24
DLAY SEC
Bias control and ground delay time (in seconds). Programmable; see table 6-10 for more information.
25
FD PHASE
Local phase fault detector current. Programmable; see table 6-10 for more information.
26
FD GND
Local ground fault detector current. Programmable; see table 6-10 for more information.
27
BACKUP
System backup functions. Programmable; see table 6-10 for more information.
28
PH OC BU
Phase overcurrent backup. Programmable; see table 6-10 for more information.
29
G OC BU
Ground overcurrent backup. Programmable; see table 6-10 for more information.
30
P TOC
Phase inverse time-overcurrent backup. Programmable; see table 6-10 for more information.
31
PPKUP
Phase inverse time-overcurrent pickup value. Programmable; see table 6-10 for more information.
32
PCURV
Phase inverse time-overcurrent curve select value. Programmable; see table 6-10 for more information.
33
PDIAL
Phase inverse time-overcurrent dial setting value. Programmable; see table 6-10 for more information.
34
G TOC
Ground inverse time-overcurrent backup. Programmable; see table 6-10 for more information.
35
GPKUP
Ground inverse time-overcurrent pickup value. Programmable; see table 6-10 for more information.
36
GCURV
Ground inverse time-overcurrent curve select value. Programmable; see table 6-10 for more information.
37
GDIAL
Ground inverse time-overcurrent dial setting value. Programmable; see table 6-10 for more information.
38
OVHD/UGD
Overhead or underground cable. Programmable; see table 6-10 for more information.
39
OPEN CON
Open conductor action. Programmable; see table 6-10 for more information. (7)
40
STUB BUS
Stub bus active/inactive.
RFL 9300
30 de enero de 2002
B e c a u s e R F L ™ a n d H u b b e l l ® h a v e a p o l i c y o f c o n t i n u o u s p r o d u c t i mp r o v e me n t , we r e s e r v e t h e r i g h t t o c h a n g e d e s i g n s a n d s p e c i fi c a t i o n s wi t h o u t n o t i c e .
>> La tabla continua en la próxima pagina <<
>> refiérase a la pagina 6-24 para las notas <<
6-21
RFL Electronics Inc.
(973) 334-3100

Publicidad

Tabla de contenido
loading

Tabla de contenido