Tabla 8-1. Parámetros programables, Sistema de comparación de caga para dos terminales RFL 9300
No.
Display
PH BIAS
20
21
GND BIAS
22
BIAS CTL
GND DLY
23
24
DLAY SEC
25
FD PHASE
26
FD GND
BACKUP
27
28
PH OC BU
29
G OC BU
PH TOC
30
P PICKUP
31
32
PH CURVE
33
PH DIAL
GND TOC
34
G PICKUP
35
36
G CURVE
37
GND DIAL
OVHD/UGD
38
39
OPEN CON
41
CM ALM D
42
DC FILT
43
DEFAULT
44
BEEPER
45
DISPLAY
XMIT ADD1
46
COM MODE
48
49
ACT CHAN
50
G B4 TRP
51
RS232 BD
RS232 PR
52
141
SEL POLE
145
TRIP RLS
RFL 9300
15 de diciembre de2002
B e c a u s e R F L ™ a n d H u b b e l l ® h a v e a p o l i c y o f c o n t i n u o u s p r o d u c t i mp r o v e me n t , we r e s e r v e t h e r i g h t t o c h a n g e d e s i g n s a n d s p e c i fi c a t i o n s wi t h o u t n o t i c e .
Definition
Phase bias
Ground bias
Bias control
Ground delay
Bias control and ground delay time
Local phase fault detector current
Local ground fault detector current
System backup functions
Phase overcurrent backup
Ground overcurrent backup
Phase inverse time overcurrent enable/disable
Phase inverse time overcurrent pickup value
Phase inverse time overcurrent curve select
Phase inverse time overcurrent dial setting
Ground inverse time overcurrent enable/disable
Ground inverse time overcurrent pickup value
Ground inverse time overcurrent curve select
Ground inverse time overcurrent dial setting
Overhead or underground cable
Open conductor action
Communications alarm delay
Dc filter for tapped load applications
Reset Parameter #'s 20 - 44 to default values
Enable/disable audible beeper
Adjust display intensity
Select transmit address 1
Selects hot standby communications mode.
Selects channel for hot standby communications.
Guard before trip
Selects RS-232 baud rate
Selects RS-232 handshaking protocol
Selective pole relaying enable/disable
Selects trip release algorithm
<< Refiérase a la pagina 8-7 para notas >>
8-8
Setting
3.0 A
1.5A
ENABLE *
DISABLE
1000 ms/30 s *
6A
0.5A
ENABLE
31.875 A *
31 A *
ENABLE
31.875A
USA1
USA1
ENABLE
31.0A
USA1
USA1
UGD *
ALARM (6) *
ENABLE *
ENABLE *
DISABLE (2) *
ENABLE (3) *
)
Brightest (4
*
0000
AUTO *
)
CH1 or CH2 (5
*
ENABLE
9600 *
XON/XOFF *
DISABLE (7)
TRIP+100