4 Installation location
(1)
(7)
(1)
38
Ventilation system
|
Please note:
Central inverters and devices like transformers, fuse distributors or
|
system monitoring components (e.g. PC, servers) emit heat.
The generated warm exhaust air must be deflected.
|
The cooler the environment of the central inverter, the greater its
|
level of efficiency and the longer its service life.
Designed to bear the weight of the device (see Specifications, page 87)
|
and of the transport vehicle.
Please note:
Under-engineered foundations may collapse thus creating a life-
|
threatening situation.
Designed to match the device footprint (see Specifications, page 87).
|
Please note:
Position of the device feet and the air duct.
|
Manufacturer recommendation: Use a raised floor for ventilation or
|
a base with a grille (mesh size: 8–10 mm) to protect against
unauthorised access.
(1)
(6)
(1)
4.1:
Underside of the device
(1) Device foot
(2) AC connection bar PE
(3) Cable mounting rails with cable fastenings
(4) Air duct of the device
(5) DC connection area
(6) AC connection area
Operating manual
(5)
Transformerless central inverter
(1)
(2)
(3)
(4)
(1)