Specifications
Transformerless central inverter
All central inverters have the following characteristics:
Protection type against environmental influences: IP 20 acc. to IEC
|
60529.
Protection class I in accordance with EN 60529.
|
Maximum permissible relative humidity 95%, non-condensing.
|
Switch on automatically if there is sufficient solar generator power.
|
In the event of overload, adjusts the operating point to the solar
|
generator characteristic curve.
Maximum Power Point Tracking (≥ 99% accuracy).
|
Earth fault monitoring at DC input.
|
Integrated earthing kit (solar generator) including series fuse.
|
AC surge voltage protection, type I and type II in accordance with DIN
|
EN 61643-11/-12.
Touchscreen display with 2 GB memory capacity.
|
Interference resistance (EMC) in accordance with DIN EN 61000-6-
|
4:2007-09.
Transient emissions (EMC) in accordance with DIN EN 61000-6-
|
2:2006-03.
Voltage changes, voltage fluctuations and flicker in accordance with
|
DIN EN 61000-3-11: 2001-04.
Auxiliary power supply
Single phase
|
230 V -10%, +15% (according to EN 50160)
|
50 Hz
|
TN grid (L1, N, PE)
|
Necessary (external) fuse: 16 A, type B or similar.
|
Configurable values
Power factor Cos ϕ: 0.7 inductive up to 0.7 capacitive.
|
Grid characteristics (voltage and frequency) in accordance with
|
country-specific standards and requirements of the energy supply
company.
Delay after a grid malfunction (up to 900 s).
|
Response time after a grid malfunction (0.1–60 s).
|
Connections present on central inverters:
4 DC input connections
|
Operating manual