Access To Measurements And Personalisation Data - Eaton Pulsar Serie Manual De Instalación Y Usuario

Ocultar thumbs Ver también para Pulsar Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 93

4. Access to measurements and personalisation data

Insert the Solution-Pac CD-ROM in the drive.
On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the
Personal Solution-Pac software.
Then select "Settings", "Advanced settings" and "UPS settings".
Note that the Linux/Unix/MacOS versions of Personal Solution-Pac software do not offer this possibility.
It is possible to modify the settings listed below (detailed comments are available in the Personal Solution-Pac
software).
Main-output personalisation
Function
Output voltage on battery power
Overload alarm threshold
Voltage-threshold personalisation
Function
High threshold for transfer to battery
Low threshold for transfer to battery
Fader activation threshold
Booster activation threshold
Maximum input-voltage range
(1) Low threshold for transfer to battery: 150 V.
UPS-sensitivity personalisation
Function
UPS-sensitivity level
UPS ON/OFF personalisation
Function
Automatic start
Cold start
Forced shutdown
Energy-savings mode
UPS ON/OFF controlled by software
Battery level before restart
Battery personalisation
Function
Battery-test intervals
Low-battery warning
Battery protection against deep discharge
Audio alarm
Factory setting
230 Volts AC
105%
Factory setting
294 Volts AC
160 Volts AC
265 Volts AC
184 Volts AC
Disabled
Factory setting
Normal
Factory setting
Enabled
Enabled
Enabled
Disabled
Enabled
0%
Factory setting
Weekly
20%
Enabled
Enabled
Other available settings
200/208/220/240 Volts AC
30/50/70%
Other available settings
271 to 294 Volts AC
160 to 180 Volts AC
244 to 265 Volts AC
184 to 207 Volts AC
(1)
Enabled
Other available settings
High or low
Other available settings
Disabled
Disabled
Disabled
Enabled
Disabled
0 to 100%
Other available settings
No test / daily test / monthly
test
0 to 100%
Disabled
Disabled
34008235EN/AC - Page 15

Publicidad

Tabla de contenido
loading

Tabla de contenido