4. Access to Maintenance and Personalization Data
Insert the Solution-Pac CD-ROM in the drive.
w On the first navigation screen, select «Point to Point solution» and follow the instructions on how to install the
Personal Solution-Pac software.
w Then select «Settings», «Advanced settings» and «UPS settings».
Note that the Linux/Unix/MacOS versions of Personal Solution-Pac software do not offer this possibility.
It is possible to modify the settings listed below (detailed comments are available in the Personal Solution-Pac
software).
Main-output personalization
Function
Output voltage on battery power
Overload alarm threshold
Voltage-threshold personalization
Function
High threshold for transfer to
battery
Low threshold for transfer to battery 89 Volts AC +3%
Fader activation threshold
Booster activation threshold
Maximum input-voltage range
(1) Low threshold for transfer to battery is 70 V.
UPS-sensitivity personalization
Function
UPS-sensitivity level
Factory setting
120 Volts AC
105%
Factory setting
151 Volts AC +3%
132 Volts AC +3%
102 Volts AC +3%
Disabled
Factory setting
Normal
Other available settings
100/120/127 Volts AC
30/50/70%
Other available settings
141 to 153 Volts AC
80 to 94 Volts AC
127 to 138 Volts AC
92 to 108 Volts AC
Enabled
(1)
Other available settings
High or low
86-81710-00EN A03 - Page 19