Note: Moisture inside the motor casing will reduce the insulation resistance. If
moisture is suspected, dry the motor and repeat the measurement.
ohm

Connect the power cables

See figures B, C,
D
cable shield is the sole PE conductor for drive or motor, make sure that is has
sufficient conductivity for the PE.
1. Attach the residual voltage warning sticker in the local language next to the
control board.
2. Remove the shroud on the power cable terminals by releasing the clips and lifting
the shroud up from the sides with a screwdriver (2a). Knock out holes for the
cables to be installed (2b).
3. Cut adequate holes into the rubber grommets. Slide the grommets onto the
cables. Prepare the ends of the cables as illustrated in the figure. Two different
cable types are shown (3a, 3b). Note: The bare shield will be grounded 360
degrees. Mark the pigtail made from the shield as a PE conductor with yellow-
and-green color. Slide the cables through the holes of the bottom plate and attach
the grommets to the holes (the motor cable to the right and the input power cable
to the left).
4. Connect the motor cable:
Ground the shield 360 degrees under the grounding clamps (4a).
Connect the twisted shield of the cable to the grounding terminal (4b).
Connect the phase conductors of the cable to the T1/U, T2/V and T3/W
terminals. Tighten the screws to the torque given in table
5. Connect the input power cable as in step 4. Ground the shield 360 degrees under
the grounding clamps (5a). Connect the twisted shield to the grounding terminal
U1
M
V1
3~
W1
PE
and E. Use symmetrical shielded cable for motor cabling. If the
EN – Quick installation and start-up guide 9
D
(4c).
EN