Connect The Control Cables - ABB ACS580-01 Serie Guía De Instalación Rápida

Ocultar thumbs Ver también para ACS580-01 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 33

Connect the control cables

See figure F. It shows a example with one analog signal cable and one digital signal
cable. Make the connections according to the macro in use. The default connections
of the ABB standard macro are shown in section
1. Cut an adequate hole into the rubber grommet and slide the grommet onto the
cable. Slide the cable through a hole of the bottom plate and attach the grommet
to the hole.
2. Ground the outer shield of the cable 360 degrees under the grounding clamp.
Keep the cable unstripped as close to the terminals of the control board as
possible. For analog signal cables, ground also the pair-cable shields and
grounding wire at the SCR1 terminal. Secure the cables mechanically at the
clamps below the control unit.
3. Route the cable as shown in the figure.
4. Connect the conductors to the appropriate terminals of the control board and
tighten to 0.5...0.6 N·m.
5. Tie all control cables to the provided cable tie mounts.
EN – Quick installation and start-up guide 11
Default I/O connections
on page 12.
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN

Publicidad

Tabla de contenido
loading

Tabla de contenido