Franklin Electric SUBMONITOR CONNECT Manual De Instalación Y Funcionamiento Del Propietario página 20

Ocultar thumbs Ver también para SUBMONITOR CONNECT:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

INSTALLATION AND SETUP
Programming: Advanced Setup > Motor Protection > Current
Mod
Menu / Parameter
RW
RC
bus
404
RW
N
Service Factor
405
RW
N
Fault Reset Type
406
RW
N
Reset Re-tries
407
RW
N
Reset Delay
408
RW
N
Cooldown
409
RW
N
Cooldown Time
Locked Rotor Menu
410
RW
N
Trip/Alarm
Stall Menu
411
Trip/Alarm
Overcurrent Menu
412
RW
N
Trip/Alarm
413
RW
N
Current Level
414
RW
N
Time to Trip
415
RW
N
Fault Reset Type
416
RW
N
Reset Retries
417
RW
N
Reset Delay
Current Unbalance Menu
418
RW
N
Trip/Alarm
419
RW
N
Unbalance Level
420
RW
N
Time to Trip
421
RW
N
Fault Reset Type
422
RW
N
Reset Retries
423
RW
N
Reset Delay
20
Range
Name
1.0 to 2.0;
1.15 (Surface motor and
Custom default)
1.00 (Submersible motor
default)
multi = 0.01
0 - Manual
1 - Automatic (default)
1 to 10; default is 3
0 to 43,200; default = 900
0 - Disabled (default)
1 - Enabled
1 to 43,200; default = 300
0 - Off
1 - Fault and Alarm (default)
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
0 - Off
1 - Fault and Alarm (default)
100% to 200%;
default = 110%
1 s to 120 s; default = 30 s
0 - Manual
1 - Automatic (default)
1 to 10; default = 3
0 to 43,200; default = 900
0 - Off
1 - Fault and Alarm (default)
2 - Alarm only
1% to 50%; default = 5%
1 s to 120 s; default = 30 s
0 - Manual
1 - Automatic (default)
1 to 10; default = 3
0 to 43,200; default = 900
Description
Motor service factor; refer to the motor nameplate for this
setting.
Sets the current overload fault reset method.
When automatic reset is enabled, this sets how many
times to attempt resetting the fault.
The number of seconds between automatic resets.
Turn on or off the overload cool down run prevention fea-
ture.
Amount of overload cool down time in seconds
Choose the type of response for a locked rotor detection.
Choose the type of response for motor stall detection.
Choose the type of response for overcurrent detection.
Overcurrent threshold to signal a fault in percentage of
nominal current setting.
Amount of time in seconds for the overcurrent situation
to subside. If exceeded, then trigger the fault.
Sets the overcurrent fault reset method.
When automatic reset is enabled, this sets how many
times to attempt resetting the fault.
The number of seconds between automatic resets.
Choose the type of response for current unbalance detec-
tion.
Percentage of unbalanced current that will trigger a fault
condition.
Amount of time in seconds for the unbalanced current sit-
uation to subside. If exceeded, then trigger the fault.
Sets the unbalanced current fault reset method.
When automatic reset is enabled, this sets how many
times to attempt resetting the fault.
The number of seconds between automatic resets.

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido