Franklin Electric SUBMONITOR CONNECT Manual De Instalación Y Funcionamiento Del Propietario página 23

Ocultar thumbs Ver también para SUBMONITOR CONNECT:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Mod
RW
RC
Display Name
bus
455
RW
N
Underpower Reset 0 - Manual
456
RW
N
Underpower Retry 1 to 10; default = 3
457
RW
N
Underpower Reset
Delay
Overpower menu
458
RW
N
Trip/Alarm
459
RW
N
Overpower Level
460
RW
N
Time to Trip
461
RW
N
Fault Reset Type
462
RW
N
Reset Retries
463
RW
N
Reset Delay
Negative Power menu
464
RW
N
Trip/Alarm
Underpower menu
452
Trip/Alarm
453
Underpower Level 101 to 200; default = 125
454
Time to Trip
455
Fault Reset Type
456
Reset Retries
457
Reset Delay
Programming: Advanced Setup > Motor Protection > System
Mod
RW
RC
Display Name
bus
Insulation Check menu
465
RW
N
Trip/Alarm
466
RW
N
Fault Resistance
467
RW
N
Alarm Resistance
SubTemp menu
468
RW
N
Trip/Alarm
469
RW
N
Trip Temp
470
RW
N
Alarm Temp
Programming: Advanced Setup > Motor Protection > System
Range
1 - Automatic
2 - Well Recovery (Submers-
ible Pump only)
1 to 43,200; default = 900
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
101 to 200; default = 125
1 to 120; default = 3
0 - Manual
1 - Automatic (default)
1 to 10; default = 3
1 to 43,200; default = 900
0 - Off (default)
1 - Fault and Alarm
2 - Alarm Only
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
1 to 120; default = 3
0 - Manual
1 - Automatic (default)
1 to 10; default = 3
1 to 43,200; default = 900
Range
0 - Off (default)
1 - Fault and Alarm
2 - Alarm Only
1 to 2000; default = 500
1 to 3000; default = 1000
0 - Off (default)
1 - Fault and Alarm
2 - Alarm Only
0 to 150; default = 40
0 to 150; default = 30
INSTALLATION AND SETUP
Description
Underpower Reset Method
When set to well recovery, the SubMonitor Connect
infinitely resets an Underpower fault condition based on
the user-selected reset delay.
Underpower Automatic Reset Attempts
Underpower Reset Delay in seconds
Choose the type of response for when an Overpower con-
dition is detected.
Over Power Level Percentage
Over Power Delay Time in seconds
Over Power Reset Method
Over Power Automatic Reset Attempts
Over Power Reset Delay in seconds
Choose the type of response for when Negative Power is
detected.
Choose the type of response for when Underpower is
detected.
Underpower Level Percentage
Underpower Delay Time in seconds
Over Power Reset Method
Underpower Automatic Reset Attempts
Underpower Reset Delay in seconds
Description
Insulation Check Enable. This measures an approximate
resistance between the W circuit and earth ground.
Insulation Resistance Fault Level
Insulation Resistance Alarm Level
SubTemp Motor Protection Enable
SubTemp Fault Trip Temperature setting in °C
SubTemp Alarm Trip Temperature setting in °C
23

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido