Franklin Electric SUBMONITOR CONNECT Manual De Instalación Y Funcionamiento Del Propietario página 43

Ocultar thumbs Ver también para SUBMONITOR CONNECT:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Mod
R/W
RC
Address Name
Bus
322
R
N
Phase A PF
323
R
N
Phase B PF
324
R
N
Phase C PF
325
R
N
kWh
326
327
R
N
Motor Insulation
328
R
N
RTD Temperature
329
R
N
SubTemp
Temperature
330
R
N
SubTemp Status
331
Not Used
332
R
N
SCR Temperature
400
RW
N
Application
401
RW
N
FLA1
402
RW
N
FLA2
403
RW
N
OL Trip Class
404
RW
N
Service Factor
405
RW
N
OL Reset
406
RW
N
OL Retry
407
RW
N
OL Reset Delay
408
RW
N
OL Cooldown
Enable
409
RW
N
OL Cooldown Time 1 to 43,200; default = 300
410
RW
N
Lock Rotor Fault
411
RW
N
Stall Enable
412
RW
N
Over Cur Enable
Choices/Range
-1.00 to 1.00
multi =
0.0 1
-1.00 to 1.00
multi =
0.0 1
-1.00 to 1.00
multi=
0.0 1
0 to 4,294,967,295
0 to 65,535
-50 to 120
0 to 150
0 - Good
1 - Searching
2 - Low Signal
3 - No Signal
4 - Off
Not Used
0 to 200
0 - Custom
1 - Submersible Pump
2 - Surface Pump
1.0 to 1000.0; default = 1;
multi = 0.1
1.0 to 1000.0; default = 1;
multi = 0.1
0 - 4; default = 0/1
0 - 5 seconds or less
1 - 10 seconds or less
2 - 20 seconds or less
3 - 30 seconds or less
4 - Submersible Motor
1.00 to 2.00; default = 1.15
multi = 0.01
0 - Manual
1 - Automatic (default)
1 to 10; default = 3
0 to 43,200; default = 900
0 - Disabled (default)
1 - Enabled
0 - Off
1 - Fault (default)
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
0 - Off
1 - Fault (default)
Modbus RTU Communication
Description
Phase A Power Factor
Phase B Power Factor
Phase C Power Factor
Accumulated kWh
Measured insulation resistance in kΩ
Temperature reading from RTD in °C
Temperature reading from SubTemp signal in °C
Status of the SubTemp Receiver
Not Used
Temperature reading from SCR in °C
Motor application - Sets specific parameter presets based
on the selected pump application.
FLA/SFA/high speed FLA
Low-speed FLA
Sets the overload trip class:
Reduced Voltage SMS default = 0
SMS (Surface Pump) default = 1
SMS (Submersible Pump) default = 4
Motor service factor
Overload Reset Method
Overload automatic reset attempts
Overload automatic reset delay (in seconds)
Overload cooldown run prevention enable
Overload cooldown time
Locked Rotor Enable
Stall Enable
Over current protection enable
COMMUNICATIONS
43