Primary Modbus Map - Franklin Electric SUBMONITOR CONNECT Manual De Instalación Y Funcionamiento Del Propietario

Ocultar thumbs Ver también para SUBMONITOR CONNECT:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

COMMUNICATIONS
Modbus RTU Communication

Primary Modbus Map

RW = Read and Write, R = Read Only, W = Write Only
RC = Running Change (adjustable while motor is running).
Mod
R/W
RC
Address Name
bus
100
RW
Y
Auto Run
101
RW
Y
Reset Fault
102
RW
N
Reset kWH
103
RW
N
Reset Run Time
(Motor Time)
104
105
RW
N
Reset Settings
106
W
Y
Set Date
107
108
W
Y
Set Time
109
38
Range/Format/Information
0 - Off
1 - On
Write a 1 to reset this param-
eter.
Write a 1 to reset kWH
Write a 1 to reset Run Time
Write a 1 to reset parameters
back to factory defaults
MMDDYY
HHMMSS
Description
Commands the starter to run when in Auto mode. Need
to have Modbus "COM CONTROL" enabled.
Resets the fault condition when in Auto mode. Need to
have Modbus "COM CONTROL" enabled.
Resets the total accumulated kWh. Need to have Modbus
"COM CONTROL" enabled.
Resets the total accumulated run time of the motor. Need
to have Modbus "COM CONTROL" enabled.
Reserved Item; address is not available.
Resets all user settings back to factory default values.
Need to have Modbus "COM CONTROL" enabled.
Sets the system date. Only the 3 least significant bytes
are used. From least to most significant byte: year, day,
month (0x00MMDDYY)
Sets the system time. Only the 3 least significant bytes
are used. From least to most significant byte: second,
hour, day (0x00HHMMSS)

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido