Franklin Electric SUBMONITOR CONNECT Manual De Instalación Y Funcionamiento Del Propietario página 32

Ocultar thumbs Ver también para SUBMONITOR CONNECT:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

OPERATION
Protection Features
If the sequence of motor leads is correct (matches Starting Sequence in the following table), reroute the
sequence of motor wires going through the sensors (and L1, L2, and L3) to match the Rotate Clockwise 1
column. If "No Sig" or "Low Sig" continue to display, reroute the motor leads and L1, L2, and L3 to match the
Rotate Clockwise 2 column.
Starting Sequence
Motor
Sensor
Lead ID
Phase ID
T1
A
T2
B
T3
C
SubTemp Temperature Programming
Modbus Addresses for SubTemp
329 - SubTemp Temperature
330 - SubTemp Receiver Status
SubTemp Temperature Setpoint
1.
Set the SubTemp temperature Alarm to 70 °C.
2. Set the SubTemp temperature Fault to 85 °C.
3. If SubMonitor Connect (under normal operating conditions) faults at 85 °C, check the following before
contacting your installer.
a. Proper water flow around motor
b. Verify all other SubMonitor Connect protective features are set correctly (SFA, Power, Current
Imbalance, etc.
c.
Discharge valve open
If setup of Pump-Motor-Assembly (PMA) and the SubMonitor Connect appear to be in accordance with
Franklin Electric recommendations, please contact your installer and Franklin Electric representative.
Refer to
"Programming: Advanced Setup > Motor Protection > System" on page 23
SubMonitor Connect for SubTemp use.
32
Rotate Clockwise 1
Incoming
Motor
Sensor
Power ID
Lead ID
Phase ID
L1
T1
L2
T2
L3
T3
Incoming
Motor
Power ID
Lead ID
C
L1
T1
A
L2
T2
B
L3
T3
Rotate Clockwise 2
Sensor
Incoming
Phase ID
Power ID
B
L1
C
L2
A
L3
for programming the

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido