COMMUNICATIONS
Modbus RTU Communication
Mod
R/W
RC
Address Name
Bus
413
RW
N
Over Cur Level
414
RW
N
Over Cur Delay
415
RW
N
Over Cur Reset
416
RW
N
Over Cur Retry
417
RW
N
Over Cur Reset
Delay
418
RW
N
Unbl Cur Enable
419
RW
N
Unbl Cur Level
420
RW
N
Unbl Cur Delay
421
RW
N
Unbl Cur Reset
422
RW
N
Unbl Cur Retry
423
RW
N
Unbl Cur Rst Dly
424
RW
N
Grnd Flt Enable
425
RW
N
Grnd Flt Level
426
RW
N
No Cur Enable
427
RW
N
Unexp Cur Enable
428
RW
N
Out Cal Enable
429
RW
N
Max Str Enable
430
RW
N
Nominal Voltage
431
432
RW
N
Ovr Vlt Enable
433
RW
N
Ovr Vlt Level
434
RW
N
Ovr Vlt Delay
435
RW
N
Ovr Vlt Reset
436
RW
N
Ovr Vlt Retry
437
RW
N
Ovr Vlt Rst Dly
44
Choices/Range
100 to 200; default = 110
1 to 120; default = 30
0 - Manual
1 - Automatic (default)
1 to 10; default = 3
1 to 43,200; default = 900
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
1 to 50; default = 5
1 to 120; default = 10
0 - Manual
1 - Automatic (default)
1 to 10; default = 3
1 to 43,200; default = 900
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
1.0 to 10.0; default = 1.0
multi = 0.1
0 - Off (default)
1 - Fault and Alarm
2 - Alarm Only
0 - Off (default)
1 - Fault and Alarm (default)
2 - Alarm Only
0 - Off (default)
1 - Fault and Alarm (default)
2 - Alarm Only
0 - Off (default)
1 - Fault and Alarm (default)
2 - Alarm Only
120.0 to 72,000; default =
208.0 multi = 0.1
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
101 to 125; default = 110
1 to 120; default = 10
0 - Manual
1 - Automatic (default)
1 to 10; default = 3
1 to 43,200; default = 900
Description
Over current level percentage. Percent of motor FLA/
SFA. If any phase current is greater than setting for Over
Current Delay, SMC faults/alarms.
Over current delay, in seconds, to trip fault/alarm. Timer
is reset if the current drops below the motor Over Current
Level.
Over current reset method
Over current automatic reset attempts
Over current automatic reset delay time
Current unbalance protection enable
Current unbalance level percentage
Current unbalance delay to trip fault/alarm in seconds
Current Unbalance Reset Method
Current unbalance automatic reset attempts
Current unbalance automatic reset delay in seconds
Ground Fault Protection Enable
Ground Fault Level in amperes
No Current Protection Enable
Unexpected Current Protection Enable
Out of Calibration Protection Enable
Maximum Start Time Protection Enable
Nominal Voltage setting
Overvoltage Protection Enable
Overvoltage Level Percentage
Overvoltage Delay Time in seconds
Overvoltage Reset Method
Overvoltage Automatic Reset Allowed Attempts
Overvoltage Automatic Reset Delay in seconds