Electrical Connection Options
If your home has:
And you will be
connecting to:
3-wire receptacle
A UL Listed,
(NEMA type 10-50R)
250-volt
minimum,
40- or 50-amp
range power
supply cord
4-wire receptacle
A UL Listed,
(NEMA type 14-50R)
250-volt
minimum,
40- or 50-amp
range power
supply cord
3-Wire Connection: Power Supply Cord
Use this method only if local codes permit connecting chassis
ground conductor to neutral wire of power supply cord.
1. Feed the power supply cord through the strain relief on the
cord/conduit plate on bottom of range. Allow enough slack
to easily attach the wiring to the terminal block.
A
C
A. Terminal block
B. Ground-link screw
C. UL Listed strain relief
D. Power supply cord wires - large opening
2. Use
Go to section:
3-Wire
Connection: Power
Supply Cord
4-Wire
Connection: Power
Supply Cord
3. Connect line 2 (red) and line 1 (black) wires to the outer
4. Firmly tighten hex nuts.
5. Tighten strain relief screws.
6. Replace lower access cover.
B
Use this method for:
D
1. Cut out and remove part of metal ground strap, as shown.
2. Use a Phillips screwdriver to remove the ground-link screw
3
/
" (1.0 cm) nut driver to connect the neutral (white)
8
wire to the center terminal block post with 1 of the 10-32
hex nuts.
A
B
C
A. 10-32 hex nut
B. Line 2 (red) wire
C. Ground-link screw
terminal block posts with 10-32 hex nuts.
NOTE: For power supply cord replacement, use only a
power cord rated at 250 volts minimum, 40 or 50 amps,
that is marked for use with nominal 1
connection opening, with ring terminals and marked for use
with ranges.
IMPORTANT: Verify the tightness of the hex nuts.
4-Wire Connection: Power Supply Cord
New branch-circuit installations (1996 NEC)
Mobile homes
Recreational vehicles
In an area where local codes prohibit grounding through
the neutral
A. Metal ground strap
B. Discard
C. Ground-link screw
from the back of the range. Save the ground-link screw and
the end of the ground link under the screw.
E
D
D. Neutral (white) wire
E. Line 1 (black) wire
3
/
" (3.5 cm) diameter
8
A
B
C
9