Electrical Connections - baltur GI Serie Manual De Instrucciones

Two-stage progressive/omdulating heavy oil burners
Ocultar thumbs Ver también para GI Serie:
Tabla de contenido

Publicidad

BALTUR PUMP MODEL BT.....
E
N
G
L
I
S
Pump pressure regulation
H
(20 ÷ 22 bar)
Pump pressure regulation
(20 ÷ 22 bar)
FASTENING THE BURNER TO THE BOILER
The burner must be applied to the boiler's iron plate, where the
stud bolts given as standard accessories have already been fitted
in accordance with the plate drilling. It is advisable to electrically
weld the stud bolts to the internal part of the plate to avoid extrac-
ting them together with the unit's locking nuts, should be burner be
disassembled.
If the plate is not supplied with heat insulation, it is necessary to
insert an insulating protection at least 10 mm. thick between the plate
and the boiler. To fit the insulating flange between the burner and the
boiler plate, remove the end section of the combustion head.
1/4" Vacuum-meter connection
Suction
1/4" Vacuum-meter connection
Suction
Pump plate
12 / 28
0006081143_201107
Return
Pump plate
Delivery (nozzle)
1/4" Pressure gauge connection
Heating element seal
Return
Delivery (nozzle)
1/4" Pressure gauge connection
Heating element seal

ELECTRICAL CONNECTIONS

It is advisable to make all connections with flexible electric wire.
The electric lines should be at an adequate distance from hot parts.
Make sure that the electric line to which the unit will be connected
has frequency and voltage ratings suitable for the burner. Check
that the main line, the relevant switch with fuses (essential) and the
current limiter (if required) are capable of withstanding the maximum
current absorbed by the burner. For details, refer to the specific
electric diagram for each single burner.

Publicidad

Tabla de contenido
loading

Tabla de contenido