SMA SUNNY TRIPOWER 60 Instrucciones De Instalación página 34

Ocultar thumbs Ver también para SUNNY TRIPOWER 60:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

4  Service
PV-Related Events
ID
Status
message
103
PV current is
too high/
waiting
115, 260 PV ISO too
low
258
PV voltage
too high/
waiting
278
Table 4.2 PV-related events
System-Related Events
ID
Status
message
2000
2010,
2011
2012 -
2018
2030
2050
2051
2052,
2053
34
STP60-10-IA-xx-11
Description
Too many PV modules
connected in parallel. Should
only appear on newly installed
systems.
The resistance between the PV
strings and ground (PE) is too
low for the inverter to be
commissioned. The inverter
automatically performs a new
measurement after 10 minutes.
The DC voltage is too high.
DC voltage warning.
Description
Communication assembly is
booting.
The software update of the
main CPU has started / has
finished.
The software update failed.
Transmission of the grid code to
the main computer failed.
Ethernet connection is active
Ethernet connection is
disconnected
Transmission of the grid code
from the SMA Inverter
Manager to the STP 60-10 has
started / finished.
SMA Solar Technology AG / SMA Solar Technology America LLC
Measure
Check number of strings in parallel
and current ratings. Has the current
limit been exceeded? Reconnect
strings in parallel.
Make a visual inspection of all PV
cables and modules for correct
installation according to the
installation manual. The event could
indicate that the PE connection is
missing.
Make sure that PV system and layout
correspond to recommendations in
the manuals.
Make sure that PV system and layout
correspond to recommendations in
the manuals.
Measure
-
-
Restart the software update. If an
error occurs during the update,
contact Service.
If the occurs repeatedly, contact
Service.
No measures required. This error
identifies bad Ethernet cables.
No measure necessary. This error is
used, for example, to identify bad
Ethernet cables.
-
DNO SMA
PV
Service
Line
-
x
x
-
x
x
-
x
x
-
x
x
DNO SMA
PV
Service
Line
-
-
-
-
-
-
-
x
-
-
x
-
-
-
-
-
-
-
-
-
-
Installation Guide

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido