Installation Conditions - SMA SUNNY TRIPOWER 60 Instrucciones De Instalación

Ocultar thumbs Ver también para SUNNY TRIPOWER 60:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

5  Technical Data

5.4 Installation Conditions

Parameters
Operating temperature range
Storage temperature
Relative humidity
Pollution degree
Environmental category IEC62109-1
Environmental class in accordance with IEC 60721-3-4
Cooling concept
Air quality - general
Air quality - coastal, heavy industrial and agricultural zones
Vibration
Enclosure protection class
UL 50E enclosure type
Maximum operating altitude above mean sea level
Installation
* Potential power reduction above 45°C (113°F) (for further information see technical information "Efficiencies and Derating")
** Installation at altitudes > 2000 m are possible on request; contact SMA Solar Technology AG for this.
Table 5.6 Installation conditions
42
STP60-10-IA-xx-11
SMA Solar Technology AG / SMA Solar Technology America LLC
-25°C to 60°C (-13°F to 140°F)*
5% to 95%, (non-condensing)
Outdoor, wet (see Section 2, page 19)
4K4H/4Z4/4B2/4S3/4M2/4C2
Class G3 (at 75% rF)
Must be measured and classified in accordance with ISA
S71.04-1985: G3 (at 75% RH)
2000 m (6500 ft) above sea level (power reductions may
occur starting at an altitude of 1000 m).**
Avoid constant contact with water.
Avoid direct solar irradiation.
Ensure adequate air flow.
Mount on non-flammable surface.
Mount upright on vertical surface.
Prevent dust and ammonia gases.
Specification
-40°C to 60°C
PD2
Forced cooling
ISA S71.04-1985
< 1 G
IP65
NEMA 3R
Installation Guide

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido