SMA SUNNY TRIPOWER 60 Instrucciones De Instalación página 35

Ocultar thumbs Ver también para SUNNY TRIPOWER 60:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

SMA Solar Technology AG / SMA Solar Technology America LLC
ID
Status
message
2054
2055
Fallback
activated
2056
Fallback
completed
Table 4.3 System-related events
Internal Events
ID
Status
message
201–
208
209, 210
211
Low fan
speed
213–
215
216–
218
219–
221
225–
240, 275
241,
242,
245, 249
Installation Guide
Description
Transmission of the grid code
from the SMA Inverter
Manager to the STP 60-10
failed.
The inverter switched to the
fallback mode after the
communication with the SMA
Inverter Manager was
interrupted.
The inverter has switched back
to normal operation after
having been in the fallback
mode due to a communication
disturbance with the SMA
Inverter Manager.
Description
The internal temperature of the
inverter is too high.
Voltage in DC link is too high.
Fan speed is too low.
Internal error. Voltage
measured before and after the
relay differs too much.
Current measured on AC side is
too high.
Internal error. Voltage
measured before and after the
relay differs too much.
Failure in memory/EEPROM.
Internal communications fault.
Measure
If this event occurs frequently,
contact Service.
Measure
Verify that no objects or dust are on
top of the inverter and make sure
that the air ducts are clear and not
blocked.
If the event persists, reset the inverter
by disconnecting DC and AC. If the
event is repeated, check the
maximum PV voltage using the
display to see if it is above the limits.
Check whether the inverter fan is
blocked.
Contact Service.
Contact Service.
Contact Service.
Restart the inverter. If the event
persists, call Service.
Restart the inverter. If the event
persists, call Service.
4  Service
DNO SMA
Service
Line
-
-
-
-
-
-
-
-
-
DNO SMA
Service
Line
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
STP60-10-IA-xx-11
PV
PV
35

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido