SMA SUNNY TRIPOWER 60 Instrucciones De Instalación página 36

Ocultar thumbs Ver también para SUNNY TRIPOWER 60:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

4  Service
ID
Status
message
248
252–
254
243, 263
279
280
281
282
283
323
Table 4.4 Internal events
36
STP60-10-IA-xx-11
Description
Internal CPU error.
Current measured on AC side is
too high.
Internal error.
Temperature sensor error.
Self-test 24-hour timeout.
Self-test must run at least once
per 24 hours.
Too many RCMU events during
the past 24 hours. Only four
automatic reconnect attempts
after event 34 is allowed during
a 24-hour period. The inverter
will automatically try to
reconnect after a certain
period.
Grid code settings invalid.
Gatedrive error.
Internal fan error. Maximum
output power has been
reduced.
SMA Solar Technology AG / SMA Solar Technology America LLC
Measure
Restart the inverter. If the event
persists, call Service.
If the event repeats, call Service.
Restart the inverter. If the event
persists, call Service.
If the event persists, call Service.
None.
Wait up to 24 hours. If event 34
recurs, follow the action for event
34.
Restart the inverter. If the event
persists, ask Service to generate a
new grid code file or reselect a
standard grid code.
Restart the inverter. If the event
persists, call Service.
If the event repeats, call Service.
DNO SMA
PV
Service
Line
-
x
-
-
x
-
-
x
-
-
x
-
-
-
-
-
x
-
-
x
-
-
x
-
-
x
-
Installation Guide

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido