The Blocksystem FS must be installed in locations were good air circulation and exchange is guaranteed and must be installed only on
a vertical wall. For different types of installation, contact the manufacturer. When positioning the moto-condensing units and the
evaporator, comply with the minimum heights reported in Figure 3.
Figure 3 - Minimum heights
ATTENTION:
During installation, leave sufficient space around the machine to perform the maintenance in safe conditions.
For correct machine operation, the following minimum cell wall thicknesses are recommended (polyurethane insulation): MBP and
HBP cell insulation thickness 60 mm; LBP cell insulation thickness 100 mm.
4.3.1. SF Series Installation Method
Use the following procedure for machine installation:
1.
Lift the machine using suitable lifting equipment and the appropriate hooks.
2.
Attach the condenser part to the vertical wall using 4 screws as indicated in Figure 4, keeping a minimum of 400 mm from the
ground (Figure 3).
3.
Proceed with attaching the evaporator to the inside of the cell using 4 steel bolts (Figure 4).
4.
Extend the drainpipe from the evaporator tray (minimum temperature resistance: 90°C) to the outside of the cell with a rubber
hose, creating a siphon (Figure 4). Please Note: for models MBP and LBP, insert the discharge heater inside the hose.
5.
Drill a hole on the wall of the cell (Figure 4) for the outlet and suction pipes and for the water drain pipe.
6.
Drill a hole for the electrical cables: power supply cable, evaporator fan cable, discharge heater cable, defrosting heater cable,
cell light cable.
Figure 4 - Installing the machine.
Before proceeding with installation, a refrigeration system project must be developed which
defines: a) all components of the refrigeration system such as the condensing unit, evaporator,
capillary, thermostatic valve, cell front, piping dimension, safety components, etc.; b) location of
the system; c) piping layout.
set
on
off
Legend
S = Suction pipe
D = Drain pipe
Sf = water drain siphon
R = discharge heater (only for MBP and LBP models)
FS Pag. 47 Rev 00 02/11