UK
Code
Level Descr.
List of -FAn fan parameters
FSt
1
Fans switch on temperature
Fot
1
Fans switch off temperature
FAd
1
Fans switch on and off differential
Fdt
1
Post-dripping time
The time after the dripping phase, during which the fans remain switched
off
dt
1
Dripping time
The time after a defrosting cycle during which the compressor and the
evaporator are stopped in order to favour evaporator dripping
dFd
1
Fans deactivated during defrosting
0 = fans activated (operation set from FPt)
1 = fans deactivated
FCO
1
Fans activated with compressor off
0 = fans deactivated
1 = fans activated (operation set from FPt)
2 = fans in duty cycle operation
Fon
1
Fans ON time during duty cycle operation (FCO=2)
FoF
1
Fans OFF time during duty cycle operation (FCO=2)
List of -ALr alarm parameters
AFd
1
Temperature alarm threshold differential
This sets the re-entry temperature threshold after a high- or low-
temperature alarm condition
HAL
1
Maximum alarm threshold
Above this value (absolute or referred to the setpoint) an alarm is
triggered
If the reference is relative, the unmarked value is added to the setpoint
LAL
1
Minimum alarm threshold
Below this value (absolute or referred to the setpoint) an alarm is
triggered
If the reference is relative, the unmarked value is subtracted from the
setpoint
PAO
1
Temperature alarm delay at power-on
dAO
1
Temperature alarm delay after defrost
The time, starting from the end of the dripping phase, during which no
alarm is signalled.
In the event of contemporaneous network defrosting, the time refers to
the defrosting end command
OAO
1
Temperature alarm delay after door closure
The time, after the door is closed again and during which no alarm is
signalled
dAt
1
Defrosting alarm timeout enabling
This enables the signalling of any defrosting end due to the maximum
time limit being reached (timeout).
0 = signal disabled
1 = signal enabled
List of -diS display parameters
ndt
1
Decimal point display
0 = display without decimal point
1 = display with decimal point.
ddL
1
Display during the defrosting phase
0 = normal display (as set from the ddd par.)
1 = freezes the temperature value displayed at the start of defrosting
until the end of defrosting and the reaching of the setpoint
2 = "dF" until the end of defrosting and the reaching of the setpoint
The ddL parameter can be controlled only if the standard display (ddd
par.) includes the adjustment probe (probe 1 or network probe)
Ldd
1
Defrosting display block timeout
The time, starting from the end of defrosting (end of dripping
phase),after which the normal display is in any case restored
probe2 ≥ FSt: fans off
Fot ≤ probe2 < (FSt – FAd):
fans on
probe2 < (Fot – FAd): fans
off
Range
Unit
MBP
-50.0 ...
°C [°F]
199.0
-50.0 ...
°C [°F]
-50
199.0
1.0 ... 90.0
°C [°F]
0 ... 60
min
0 ... 60
min
0,1
flag
0 ... 2
1 ... 60
min
15
1 ... 60
min
15
1.0 ... 90.0
°C [°F]
-50.0 ...
°C [°F]
10
199.0
-50.0 ...
°C [°F]
-10
199.0
0 ... 10
h
0 ... 999
min
60
0 ... 10
h
0,1
flag
0,1
flag
0,1,2
0 ... 255
min
FS Pag. 53 Rev 00 02/11
LBP
HBP
8
-5
50
-50
-50
2
2
2
1
2
0
2
2
0
1
1
0
0
0
0
15
15
15
15
2
2
2
10
10
-10
-10
4
4
4
60
60
0
0
0
0
0
0
1
1
1
0
0
0
6
6
6