5) Controlling combustion
To keep consumption down and, more importantly, to prevent
serious problems, adjust combustion using the instruments
provided. It is absolutely essential to ensure that the percentage
of carbon monoxide (CO) does not exceed the maximum value
permitted, 0.1% (use a combustion analyser). The guarantee will
not cover burners burning liquid propane gas (L.P.G.) in installa-
tions in which these measures have not been applied.
Minimum temperature
990 l tank
3000 l tank
5000 l tank
E
N
DIAGRAM ILLUSTRATING THE PRINCIPLE OF L.P.G. PRESSURE REDUCTION IN TWO STAGES FOR BURNER
OR BOILER
G
L
Pressure gauge and pressure intake
I
S
H
1st step reducer
Output @ 30 mbar
Flow rate @ double
the maximum re-
quired by the user
Tank
L.P.G.
- 15 °C
- 10 °C
1.6 Kg/h
2.5 Kg/h
2.5 Kg/h
4.5 Kg/h
4 Kg/h
6.5 Kg/h
2nd step reducer
Output @ 30 mbar
Flow rate @ double the maximum required by the user
Filter (steam type)
Pressure intake
Filter (steam type)
2nd interval reducer
Output @ 30 mbar
Flow rate @ double the maximum
required by the user
0006081225_200912
- 5 °C
3.5 Kg/h
6.5 Kg/h
11.5 Kg/h
Filter
Vibration-proof joint
Ball cock
14 / 14
- 0 °C
+ 5 °C
8 Kg/h
10 Kg/h
9 Kg/h
12 Kg/h
16 Kg/h
21 Kg/h
Burner
Filter
Freestanding or wall-mounted boiler