8. LCD Display and Settings
5. Battery Setup
Route: Main Screen  Setting Menu  BATTERY SETUP
BAT RATING VOLT (V): The default setting is 144.
TYPE (AH): Sets the battery rating. The default setting is SUT20K: 20AH, SUT30K and SUT40K: 30AH, SUT60K: 40AH.
LOW BATTERY ALARM (V): The default setting is 132.
SHUTDOWN VOLT (V): The default setting is 120V.
BATTERY NUMBER: The default setting is 12. Do not change the default setting.
Install Date (Y-M-D): Battery's actual install date.
Replace Date (Y-M-D): Battery's replacement date.
Use function keys (
), (
6. Battery Test
Route: Main Screen  Setting Menu  BATTERY TEST
Auto Deep Discharge: There are four settings: OFF, 30D, 60D and 90D (D = Days). The default setting is OFF.
Manual Test: Initiates the start of a battery manual test. The test time is five minutes. If the battery's voltage is lower than 132V, the
result is fail. If above, the result is pass.
Clear Test Result: Clears the battery test result.
Use function keys (
), (
) and (
) to change the BATTERY SETUP setting.
) and (
) to change or initiate the BATTERY TEST setting.