Appendix 1 : Technical Specifications - Tripp-Lite SmartOnline SUT20K Manual Del Propietário

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Appendix 1 : Technical Specifications

Model
CAPACITY (conditional PF de-rating to 0.9)
TOPOLOGY
INPUT
Voltage
Voltage Range
Phase
Operating Frequency
Frequency Range
Power Factor
THDi
Inverter Bridge
OUTPUT
Voltage
AC Voltage Regulation
Power Factor
Frequency
Frequency Range
Overload
AC mode
Crest Factor
Harmonic Distortion
Output Waveform
BYPASS
Automatic Bypass
Manual Maintenance Bypass
Transfer Time
Default Bypass Voltage Tolerance
Overload
BATTERY
Battery Type
Battery Capacity
Nominal Voltage
Float Voltage
Boost Voltage
End of Discharge Voltage
Battery Storage Time
Minimum
Battery Charger
Maximum
Capacity
Default
SUT20K
20kVA / 20kW
Voltage and Frequency Independent (VFI) True On-Line Double Conversion
Range Derated from 100% to 63% load: 125~187VAC (Ph-Ph), 72~108VAC (Ph-N)
208/220V (Ph-Ph), (3-ph, 4 wire, neutral reference to bypass neutral)
12V/9AH
12 x 4 strings
1A
10A
5A
SUT30K
30kVA / 30kW
208/220V (Ph-Ph), 120/127V (Ph-N)
Range Full Load: 187~253VAC (Ph-Ph), 108~146VAC (Ph-N)
3-phase, neutral and ground
50/60 Hz (selectable)
40~70 Hz
>0.99%
IGBT technology
+/- 1%
50/60 Hz (selectable)
+/- 0.05 Hz
105%: continuous
106 – 125%: 10 min.
126 – 150%: 1 min.
>150%: 1 sec.
<3% (Linear load)
Pure sinewave
Standard
Standard
<= 1ms
±15%
Refer to capability of Bypass Breaker
Maintenance-free sealed valve-regulated lead acid (VRLA)
12 x 6 strings
+/- 144V
+/- 163.2V (+/- 2V)
+/- 168V (+/- 2V)
+/- 120V (+/- 2V)
6 months (without recharge, 77°F/25°C)
1A
10A
7.5A
42
SUT40K
40kVA / 40kW
<4%
1
3:1
12 x 6 strings
1A
20A
7.5A
SUT60K
60kVA / 60kW
12 x 8 strings
1A
20A
10A