Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

8. LCD Display and Settings

8.2 Setting Menu

Route: Main Screen  Setting Menu
Settings can only be modified when the UPS is in Bypass Mode. Press and hold for 3 seconds. While in Bypass Mode, press function
keys (
) and (
) to enter the Setting Menu shown below:
Use function keys (
) and (
& test, parallel and advanced settings.
1. Local Setup
Route: Main Screen  Setting  LOCAL MENU
The default setting of DATE and TIME is GMT.
The default setting of PASSWORD is 0000
Use function keys (
), (
2. Bypass Setup
Route: Main Screen  Setting  BYPASS MENU
The range of this option is 5~15%. The default setting of VOLT RANGE (Upper) is 15%.
The range of this option is 5~15%. The default setting of VOLT RANGE (Lower) is 15%.
The range of FREQ RANGE can be reduced. The default setting of FREQ RANGE is +/-3.0.
Only when bypass input voltage is within the range of BYPASS SETUP can the UPS provide output voltage. Use function keys (
(
) and (
) to change the BYPASS SETUP setting. Press (
) to view or change the UPS system's local, bypass, output, charger, battery, battery test, control
) and (
) to set the DATE, TIME and PASSWORD.
) to confirm selection when prompted.
33
),

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido