PIPE TABLE FOR BURNERS MOD. BT 40 - 50 - 180 - 250 DSN 4T WITH 5°
E FUEL AT 50° C (40° E AT PUMPING TEMPERATURE 5° C)
PUMP AXIS
PUMP AXIS
PUMP AXIS
GRAVITY FEED SYSTEM
1- Tank
2- Feed pipe
3- Mesh filter
4- Pump
GRAVITY SYSTEM WITH FEED FROM THE TOP OF THE TANK
1- Tank
3- Mesh filter
4- Pump
6- Intake pipe
INTAKE SUPPLY SYSTEM
Note For any components missing in the pipes, comply with current regulations.
H
Difference in level between min. level in tank and pump axis.
L
To t a l l e n g t h o f e a c h p i p e i n c l u d i n g t h e v e r t i c a l s e c t i o n
Deduct 0.25 m for each elbow or gate.
13 / 40
0006081310_201211
5- Degassifier
6- Intake pipe
7- Burner return pipe
8- Automatic shut-off device with burner off
9 - Non-return valve
H meters
7- Return pipe
8- Automatic shut-off device with burner off
9 - Non-return valve
10- Foot valve
H meters
1- Tank
3- Mesh filter
4- Pump
6- Intake pipe
7- Return pipe
10- Foot valve
L Total in meters
Ø = 1" ½
Øi. 41 mm
1
35
35
1.5
40
40
2
50
50
2.5
50
50
L Total in meters
Ø = 1" ½
Øi. 41 mm
1
35
35
1.5
40
40
2
50
50
2.5
50
50
Dimension P = 3.5 m (max)
H
L Total in meters
meters
Ø = 1"½
Ø 41mm
0.5
25
25
1
20
20
1.5
15
15
2
10
10
2.5
5
5