AIR REGULATION SERVOMOTOR FOR SEPARATE PUMP MOTOR
The air regulation servomotor model CONECTRON LKS 160 is used on burners BT 250 / 300 / 350 DSN 4T in 60Hz version
STARTER MOTOR ADJUSTMENT FOR 1ST STAGE AIR GATE CONTROL
I
2ND STAGE AIR REGULATION CAM (60°)
III
CAM NOT USED ( . . . °)
III
1ST STAGE AIR REGULATION CAM (20°)
IV
2ND STAGE VALVE CONTROL CAM (40°)
STARTER MOTOR ADJUSTMENT FOR 2ND STAGE AIR GATE CONTROL
I
2ND STAGE AIR REGULATION CAM (60°)
II
TOTAL AIR CLOSURE (BURNER STOPPED)( 0°)
III
1ST STAGE AIR REGULATION CAM (20°)
IV
2ND STAGE VALVE CONTROL CAM (40°)
REFERENCE INDEX
REFERENCE INDEX
28 / 40
0006081310_201211
ADJUSTABLE CAMS
ADJUSTABLE CAMS