Configuration; Dip Switches - Siemens REV17 Serie Instrucciones De Montaje

Ocultar thumbs Ver también para REV17 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 15
Configuration and function check REV17.
1

Configuration

1.1

DIP switches

ON /
OFF
Sensor calibration on
See
1.1.1
Sensor calibration off
Setpoint limitation
16...35 °C
1.1.2
Setpoint limitation
3...35 °C
Temperature display °F
1.1.3
Temperature display °C
PID self-learning
PID 6
1.1.4
PID12
2-Point
1.1.1 Sensor calibration: DIP switch 1
Set the DIP switch to ON and press the DIP switch reset button:
The display shows CAL. The room temperature currently acquired
blinks.
Press
or
to make a recalibration of max. ± 5 °C. To save
the entry, set the DIP switch to OFF and press the DIP switch reset
button (also refer to Fig.
).
1.1.2 Setpoint limitation: DIP switch 2
DIP switch ON:
Setpoint limitation 16...35 °C
DIP switch OFF:
Setpoint limitation 3...35 °C
(factory setting)
Save the entry by pressing the DIP switch reset button.
1.1.3 Temperature display in °C or °F:
DIP switch 3
DIP switch ON:
Temperature display in °F
DIP switch OFF:
Temperature display in °C
(factory setting)
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
).
1.1.4 Control action: DIP switches 4 and 5
DIP switch 4 ON and 5 ON:
Adaptive control for all types of application.
DIP switch 4 ON and 5 OFF:
For fast controlled systems, applications at locations with
great temperature variations.
2
Accessing the expert level
Move the selector slider to the RUN position and press simultaneously
seconds, press simultaneously
access the expert level for making the settings on that level.
Starting with code 00, the display shows the choice of languages. Navigation on the expert level is made possible with
settings by pressing
.
The expert level is quit by pressing the operating mode selection button
6/40
1
2
3
4
Factory setting: All DIP switches
PID self-learning
PID 6
and
for 3 seconds, release
5
6
7
When changing one or several
DIP switch positions, a DIP
switch reset must be made by
pressing the DIP switch reset
button (also refer to Fig.
Otherwise, the previous
settings will be maintained!
OFF
DIP switch 4 OFF and 5 ON:
For normal controlled systems, applications at locations
with normal temperature variations.
DIP switch 4 OFF and 5 OFF:
For difficult controlled systems, 2-position controller with
a switching differential of 0.5 °C (factory setting).
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
1.1.5 Periodic pump run: DIP switch 6
Can only be used when circulating pump or valve is controlled!
This function protects the pump or valve against seizing during
longer off periods. Periodic pump run is activated for 3 minutes
every 24 hours at 12:00 (display showing symbol
DIP switch ON:
DIP switch OFF:
Save the entry by pressing the DIP switch reset button.
1.1.6 Radio clock: DIP switch 7
Can only be used with REV..DC (with integrated DCF77 receiver for
time signal from Frankfurt)!
DIP switch ON:
DIP switch OFF:
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
1.1.7 DIP switch reset
When changing one or several DIP switch positions, press the DIP
switch reset button to make a DIP switch reset.
Otherwise, the previous settings will be maintained!
(Also refer to Fig.
and
for 3 seconds, then release the buttons and, within 3
and keep
depressed for another 3 seconds. This enables you to
on display (also refer to Fig. G).
.
02.02.2010
Periodic pump run on
Periodic pump run off
Quartz
Radio clock
DIP switch reset
ON
1
2
3
4
5
6
)
PID 12
2-Point
).
Pump run on (also refer to Fig.
Pump run off (factory setting)
quartz
Clock runs on built-in
Time signal DCF77 from Frankfurt
).
).
and
See
1.1.5
1.1.6
1.1.7
7
8
9
).
)
. Confirm the
CE1G2203xx

Publicidad

Tabla de contenido
loading

Tabla de contenido