Kemper CleanAirTower Instrucciones De Servicio página 53

Ocultar thumbs Ver también para CleanAirTower:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 171
Note on connection to the mains supply for products with extraction capacity control
DANGER
Danger of electric voltage!
Products with extraction power control (frequency inverters) are intended for protection
by line protection fuses.
If the product is operated on a mains supply with a residual current circuit breaker
(RCCB) connected upstream, the following must be observed.
Since the operation of the frequency inverter on the protective earth conductor can
cause a direct current, the residual current circuit breaker (RCCB) connected in series
with the mains must meet the following requirements.
Category type:
Type B
Type B
Type B
Type B
Type B
CAUTION
The product can produce noise, please refer to information in the technical data. In
connection with other machines and/or local conditions, a higher noise level can occur
at the operation site of the product. In this case, the operating company is obliged to
provide the operating personnel with the appropriate protective equipment.
WARNING
Danger from mobile radiation
Mobile radiation can affect electronic and medical devices.
The product:
Do not use near medical devices such as pacemakers, insulin pumps and the like
Do not use in hospitals, petrol stations and medical facilities
Do not use near high-precision electronic equipment
Do not operate near strong electromagnetic fields
1502828-01
Rated current
40 A
63 A
80 A
100 A
125 A
Tab. 14: Requirements for residual current circuit breaker
Tripping fault
current
30 mA
300 mA
30 mA
300 mA
30 mA
300 mA
30 mA
300 mA
30 mA
300 mA
- 53 -
EN
Note
short time-delayed
short time-delayed
short time-delayed
short time-delayed
short time-delayed

Publicidad

Tabla de contenido
loading

Tabla de contenido