Out Of Box Functionality - Lutron Energi Savr Node 0-10 V Softswitch Guia De Instalacion

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Energi Savr Node
Sample application: Out of Box Functionality (requires no commissioning)
Zone 3
Daylight
Sensor
Room 3
Room 1
Daylight
Sensor

Out of Box Functionality

This section describes the default functionality that the unit will
present when first installed.
Inputs (Occupancy, Daylight, IR, and Switch):
• Input group 1: controls zone 1.
• Input group 2: controls zone 2.
• Input group 3: controls zone 3.
• Input group 4: controls zone 4.
Occupancy Sensors (Occ)
• Corresponding zones will turn on when the occupancy sensor is in
the occupied state (closed) and off when in the unoccupied state
(open).
Daylight Sensors (Photo)
• Corresponding zones will turn on when light sensed by daylight
sensor falls below the factory preset level.
• Corresponding zones will turn off when light sensed by daylight
sensor rises above the factory preset level.
• QSN-4T16-S only: Corresponding zone light levels will raise or
lower when light sensed by daylight sensor falls or rises based
on a factory default setting.
IR Receivers (IR)
• See IR Receiver literature for compatible transmitters.
• Corresponding zones respond to on, off, and Scene commands
from compatible IR transmitters.
• QSN-4T16-S only: Corresponding zones respond to Raise and
Lower commands from compatible IR transmitters.
Lutron
10
|
®
0-10 V / Softswitch
TM
Wired
to input
group 3
Energi Savr
Node unit
Occupancy
Sensor
Zone 1
Occupancy
Sensor
Wired
to input
group 1
|
Installation Guide
®
Wired
to input
group 4
Occupancy
Sensor
Occupancy
Zone 2
Sensor
Wired
to input
group 2
NEC
Class 2/PELV Dry Contact Closure (Switch)
®
• Maintained closure or open toggles corresponding zone(s)
between preset and off.
Contact Closure Input (CCI)
• Momentary closure from a normally-open (NO) dry contact
closure device will result in all zones being turned off.
Emergency Contact Closure Input (Emerg)
• If the Emergency input is open, the Energi Savr Node unit will
enter Emergency Mode, which will turn on all loads and disable
local zone control and control from sensors and QS devices.
• When the Emergency input is closed or jumpered, Energi Savr
Node unit zones will return to the settings or levels they were at
prior to entering Emergency Mode.
seeTouch
QS Wallstations
®
• All seeTouch QS lighting wallstations are Scene keypads by
default.
• QSN-4S16-S only: Scenes 1-16 will turn all the lights on.
• QSN-4T16-S only: Scenes 1-16 will dim lights to the preset
levels in the table below:
Scene #
Light Level: All Zones
1, 5-16
100%
2
75%
3
50%
4
25%
• Scene Off will turn all the lights off.
Energi Savr Node
Zone 4
Daylight
Sensor
Room 4
Room 2
Daylight
Sensor
0-10V / Softswitch
Installation Guide
TM
®

Publicidad

Tabla de contenido
loading

Tabla de contenido