Step 4: Input group wiring
To connect a daylight sensor, occupancy sensor, infrared (IR) receiver, and/or NEC
instruction sheets provided with the devices. Diagrams for the input terminals are shown below.
WARNING! Danger of Shock. May result in serious injury or death. DO NOT WIRE WHEN LIVE! Switch off power to all power
feeds via circuit breaker before wiring or servicing the Energi Savr Node unit.
Buttons and LEDs in the unit are used for programming and troubleshooting. If line voltage shield is removed, the unit must
be accessed by a certified electrician, following local codes.
Note: The Energi Savr Node unit accepts only one IR input (either daylight/IR sensor or IR receiver) per group.
Input Group Wiring
Line Voltage Shield
Input Group Wiring:
• 20 AWG to 12 AWG
(0.5 mm
to 4.0 mm
)
2
2
• Strip length: 1/4 in (6 mm)
• Torque: 5 in-lb (0.5 N
m)
Lutron
6
|
®
0-10 V / Softswitch
TM
NOTE: There are four input groups. Each group has the same
inputs as shown in the diagram below.
Group 1 shown
Com – Common
Switch – NEC Class 2/PELV Switch
IR – IR Receiver*
Daylight – Daylight Sensor
Occ – Occupancy Sensor
20 V – 20 V
Note: Maximum wire run
length to each input not
to exceed 150 ft (46 m).
IR Transmitter
Daylight/IR Sensor*
* Note: Only one IR device may be connected per input. If the IR signal
from a daylight sensor is connected, a wall control may not be connected
to the same input, and vice-versa.
**Connect the gray wire on -R model occupancy sensors.
|
Installation Guide
®
Class 2/PELV dry contact switch, refer to the
®
Group 2 shown
Occupancy Sensor
NEC Class 2
Dry Contact
Switch
Energi Savr Node
0-10V / Softswitch
TM
IR Transmitter
IR Receiver*
or Wired
Wallstation*
Installation Guide
®