Lutron Energi Savr Node 0-10 V Softswitch Guia De Instalacion página 5

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Energi Savr Node
Load Wiring (continued)
Feed-Through Wiring Example 2: 4 Circuits, Single Feed
Hot
Distribution
Neutral
Panel A
Ground
Hot
Distribution
Neutral
Panel B
Ground
Energi Savr Node
0-10V / Softswitch
TM
English
0-10 V / Softswitch
TM
Ground Bar
Neutral Wires
Zone Switching:
120-277 V
0-10 V Zones:
(QSN-4T16-S only)
Installation Guide
®
Español
|
Installation Guide
®
"A" Terminals Jumpered
0-10 V Wiring (QSN-4T16-S only)
• 20 AWG to 12 AWG (0.5 mm
• Strip length: 1/4 in (6 mm)
• Torque: 5 in-lb (0.5 N
m)
• Connect only NEC
Class 2/PELV circuits or connect only non-
®
NEC Class 2/PELV circuits to 0-10 V zones 1-4.
• 0-10 V zones 1-4 are not isolated from each other.
• Negative (–) terminals are not internally connected to each
other—both positive (+) and negative (–) connections must be
made.
• Follow all national and local codes for separation requirements.
Français
Português
LOAD
LOAD
LOAD
LOAD
Load Wiring:
• Two (2) 14 AWG to
12 AWG (2.5 mm
to
2
4.0 mm
)
2
• Strip length: 3/8 in
(8.5 mm)
• Torque: 7 in-lb
(0.79 N
m)
0-10 V Wiring
(QSN-4T16-S only)
to 4.0 mm
)
2
2
Lutron
5
|
®

Publicidad

Tabla de contenido
loading

Tabla de contenido