Energi Savr Node

Normal Operation

In normal operation, the following buttons allow the user to ac-
cess certain basic functions:
1. (Raise) — QSN-4T16-S: Raises zone light level in 1%
increments from 0-100%.
— QSN-4S16-S: Turns selected zone on.
2. (Lower) — QSN-4T16-S: Decreases zone light level in 1%
decrements from 100-0%.
— QSN-4S16-S: Turns selected zone off.
Note: On QSN-4T16-S only - For any zone, simultaneously
pressing and holding the and buttons will toggle the
zone between high end and low end.

QS Link Input(s) Setup

seeTouch QS Wallstation or GRAFIK Eye
and Scenes + Off
Assigns a seeTouch QS Wallstation or GRAFIK Eye QS unit to any
Energi Savr Node unit zone on the QS link.
1. To assign a seeTouch QS Wallstation or GRAFIK Eye QS unit to
an Energi Savr Node unit(s), simultaneously press and hold the
top and bottom buttons on the wallstation or GRAFIK Eye QS
unit for 3 seconds. The QS link enters Programming Mode. The
sensor LEDs on the Energi Savr Node unit(s) will flash sequen-
tially through each input and group.
2. To assign or un-assign desired zone(s) to a wallstation, simul-
taneously press and hold the the and buttons for the desired
zone. A blinking 'Zone' LED indicates an assigned zone.
3. To exit Programming Mode, simultaneously press and hold the
the top and bottom buttons on the wallstation or GRAFIK Eye QS
unit for 3 seconds.
Note: For more advanced programming information, refer to the
online Programming Guide at:
www.lutron.com/Softswitchenergisavrnode
Energi Savr Node
0-10V / Softswitch
TM
English
0-10 V / Softswitch
TM
QS unit - Scenes
®
Installation Guide
®
Español
Français
|
Installation Guide
®
Using LEDs to troubleshoot
WARNING! Danger of Shock. May result in serious
injury or death. DO NOT WIRE WHEN LIVE! Switch off
power to all power feeds via circuit breaker before wiring
or servicing the Energi Savr Node unit.
Buttons and LEDs in the unit are used for programming and
troubleshooting. If line voltage shield is removed, the unit
must be accessed by a certified electrician, following local
codes.
LED
LED Behavior
Continuous On
Occ
(Occupancy
1 flash per second
Sensor)
Off
Continuous On
Photo
Flashing
(Daylight
Sensor )
Off
Continuous On
IR
(Infrared
Flashing
Receiver)
Off
Continuous On
Switch
(NEC
®
Flashing
Class 2
Switch)
Off
CCI
Continuous On
(Contact Clo-
Flashing
sure Input)
Off
Emerg
Continuous On
(Emergency
Contact Clo-
Rapid flash
sure Input)
On/Flashing
3 quick flashes
QS Link
every 4 seconds
Off
Wired
Continuous On
Continuous On
Zone
Off
Português
Description
Sensor detects Vacancy
Sensor detects
Occupancy
Sensor never detected
Sensor is detected
Sensor information
transmitting on the QS link
Sensor never detected/
sensor not seeing light
Receiver is detected
IR button press detected
Receiver never detected
Switch detected/open
Switch button press
detected
Switch never detected
Contact detected/open
Contact closed
Contact never detected
Normal operation/Contact
Closed/Jumpered
Emergency Mode/Contact
Open/Jumper missing
Device transmitting/
receiving on the QS link
Communication error
Device not transmitting/
receiving on the QS link
Wired sensor
Load is on
Load is off