Occupancy Sensor Setup (continued)
Scene Mode
This step allows you to assign up to four occupancy sensors to the GRAFIK Eye QS
control unit.
Selecting Sensors
Occ Sensor
1. If not already done, associate occupancy sensors and set to
Setup
"Scene Mode".
2. Use the Master buttons to highlight "Setup" and press the
Labels
OK button to accept. The info screen will display "Searching" while
the unit detects available occupancy sensors.
3. Use the Master buttons to scroll through the list of available
occupancy sensors. When the desired sensor is displayed, press
the OK button to select it. Then choose "Assign" or "Unassign"
Saved
Searching
from the following menu and press OK. Once a sensor has been
assigned, it will appear with an asterisk (*) in the sensor list. Repeat
for additional sensors.
Note: If wireless sensors are not found, verify that they are
Sensor
x/y
xxxxxxxx
Setting the Sensor Action
yyy-yyyy
1. Press the Timeclock (back) button to return to the Occ Sensor
RF
screen. Use the Master buttons to highlight "Actions" and press the
OK button. By default, the occupied scene is set to "No Action"
and the unoccupied scene is set to "Scene Off".
Assignment
2. Use the Master buttons to highlight the scene you wish to use for
occupied status and press the OK button to accept. Repeat for the
Assign
scene you wish to use for unoccupied status. Press the OK button
Unassign
to accept.
3. Exit programming mode.
Saved
*Assigned*
Sensor
*x/y
Occ Sensor
xxxxxxxx
Actions
yyy-yyyy
3 seconds
Setup
RF
associated correctly.
Occupied Scene
Scene 1
For additional information, see the complete installation and operation guide at www.lutron.com/qs
Unoccupied Scene
Scene Off
GRAFIK Eye QS Control Unit Quick Installation and Operation Guide
OK
Saved
S aved
Master
buttons
OK
button
Timeclock
(back) button
15