Installation
3.4.4.2
FXE4000 (COPA-XE), digital communication
Valid for PROFIBUS DP, PROFIBUS PA, FOUNDATION Fieldbus, ASCII
1
2
3
4
Fig. 23
1 PROFIBUS PA:
Terminals PA+, PA-: Connection for PROFIBUS PA according to IEC 61158-2 (Profile
3.0), U = 9 - 32 V, I = 13 mA (normal operation); 17 mA (fault condition / FDE)
2 ASCII-Protocol (RS485):
Terminals Ux, V8: Scaled pulse output, passive (Optocoupler), pulse width adjustable
between 0.1 ms to 2000 ms,
Optocoupler specifications: f
0 mA ≤ I
Terminals Ux, P7: Contact output, function selectable via software e.g. to system monitor,
empty pipe, max. – min. –alarm or V/R contact output
Optocoupler specifications: f
0 mA ≤ I
Terminals A, B: Serial data link RS485 for communication using ASCII-Protocol
Terminals +, -: Current output, terminals: +/-, current ≤ 600 Ω for 0/4 to 20 mA
3 PROFIBUS DP:
Like design 2 but terminals +VD, A, B, GND connection for PROFIBUS DP according to
EN 50170
4 FOUNDATION Fieldbus:
Terminals FF+, FF-: Connection for FOUNDATION Fieldbus (H1) according to IEC 61158-
2, U = 9 ... 32 V, I = 13 mA (normal operation); 17 mA (fault condition / FDE)
5 Supply Power:
See name plate
6 Functional ground